The transmitter acquires the temperature through an RTD temperature probe or a thermocouple (double thermocouple). The transmitter can also acquire standard signals. Connection takes place through an RTD temperature probe with two-wire, three-wire, or four-wire connection.
general technical data | |
---|---|
Galvanic isolation | 1.8 kV |
Installation | On mounting rail/DIN rail 35 × 7.5 mm |
Analog input | Widerstandsthermometer in 2-, 3- und 4-Leiterschaltung; Thermoelement, Doppelthermoelement; Widerstandspotenziometer/WFG; Widerstand/Poti in 2-, 3- und 4-Leiterschaltung; Spannung 0 bis 1(10) V; Strom 0(4) bis 20 mA |
Ambient temperature | -10 to +70 °C |
Output | 0(2) to 10 V or 0(4) to 20 mA (invertible) |
Special features | Universal input for a number of sensors and standard signals, intuitive operation and configuration on the device or via USB interface with setup program, RS485 interface Modbus RTU and relay output limit value (option), intelligent additional functions such as min/max drag indicator, operating hours counter and output simulation SIL 2/SIL 3 according to DIN EN 61508 and PL c/d according to ISO 13849 (option), sensor matching for RTD temperature probe, customer-specific linearization, high degree of galvanic signal separation, connection diagram available in the display |
NAMUR compliant | NE43 |
Voltage supply | AC 110 to 240 V, DC 24 V (four-wire transmitter) |
Calibration accuracy | ± 0.05 % |
Configuration | On the device via USB interface with PC setup program |
Approval | SIL and PL, cUL, DNV GL |